1. Power supply should be sufficient and reliable, communication should be fast and smooth, and transportation should be convenient

2. For data centers that use water evaporative cooling for refrigeration, there should be sufficient water supply

3. The natural environment should be clean, and the ambient temperature should be conducive to energy saving

4. It should be far away from places that generate dust, oil smoke, harmful gases, as well as those that produce or store corrosive, inflammable or explosive substances

5. 5, should be far away from floods, earthquakes and other natural disasters potential areas

6, should be far from strong vibration and noise sources

7, should avoid strong electromagnetic field interference

8, A-class data center should not be built in the public *** parking garage

9, medium and large data centers are not suitable for building in residential and commercial areas

1) Electricity, power, electricity, and other power sources are not suitable for building the data center. p>

1) Electricity: choose adequate power supply and reliability and stability, data center power consumption is generally 1 to 2kW per square meter (confidential module 2KW-4.5KW)

2) Communications: choose to be close to the core network nodes (operator core room), and the core network nodes with fiber optic direct connection or to take other connectivity to reduce network delays

3) Transportation: from the train station, airport to reach the data center of the traffic should not be less than 2 roads

4) Water: water should be sufficient, cooling water-cooled system per kilowatt of IT equipment per day, the water consumption is about 0.1 tons (summer).

5) Climate: as far as possible to facilitate the selection of natural cooling climate conditions, the average annual temperature of about 10 degrees.